4 Pile measuring earth megger
It is an ideal device for large grounding systems.
Kew 4106 uses a test current of 80 mA (max), providing high resolution up to 1mΩ in 2Ω stage.
Optimum test current frequency
4 bands (94/105/111/128 Hz) test current frequency and advanced filtering method, which can be selected automatically or manually, reduces interference during the test.
It measures very low ground resistance measurements accurately and accurately. Soil specific resistance (ρ) is calculated automatically
Kew 4106, sticks 0.1 m. at intervals of 1.0 to 30.0 m. It allows distances up to variable.
Separate sub-results and parameters can be displayed on the screen
It shows the resistance of ground bars, the test current frequency, the voltage and frequency of interference and residual resistance.
Memorizing, Recalling Memory and Uploading to Computer
Memorizes the results of 800 measurements and displays the information in the memory on the screen.
You can transfer this information to any computer using the "Kew Report" software and USB adapter provided.
It stimulates the parasitic and high resistance of auxiliary earth bars visually.
It has international IP 54 standard and is not affected by dust and moisture.
Technical Properties | |||||
---|---|---|---|---|---|
Function | Stage | Resolution | Display stage | Accuracy | |
Grounding (Earth) Resistance Re (2/3/4 wire) Rg (Specific resistance only) | 2Ω | 0.001Ω | 0~2.099Ω | ±2%rdg. ±0.03Ω | |
20Ω | 0.01Ω | 0~20.99Ω | ±2%rdg. ±5dgt | ||
200Ω | 0.1Ω | 0~209.9Ω | |||
2000Ω | 1Ω | 0~2099Ω | |||
20kΩ | 10Ω | 0~20.99kΩ | |||
200kΩ | 100Ω | 0~209.9kΩ | |||
Auxiliary earth rods resistance Rh, Rs | (Re+Rh+Rs)*8% | ||||
Soil specific resistance ρ | 2Ω | 0.1Ω・m/ 1Ω・m Automatic Step | 0~395.6Ω・m | The accuracy of ρ-depends on the distance between the bars. Rgρ = 2π * a * Rg Distance of the bars "a": 1.0 ~ 30.0m (adjustable in 0.1m steps) | |
20Ω | 0~3956Ω・m | ||||
200Ω | 0~39.56kΩ・m | ||||
2000Ω | 0~395.6kΩ・m | ||||
20kΩ | 0~1999kΩ・m | ||||
Series interference voltage (Only AC voltage) | Voltage Upper | 50V | 0.1V | 0~50.9Vrms | ±2%rdg.±2dgt(50/60Hz)±3%rdg.±2dgt(40~500Hz) |
Frequency Fst | Automatic Stage | 0.1Hz 1Hz | 40~499.9Hz | ±1%rdg.±2dgt. | |
Screen | Screen illumination, Dot-matrix Display | ||||
Power supply (depending on measurement) |
Battery R6P x 8 400f or more (Measurement 1Ωand 2Ωstage in 30 seconds) |
||||
Size | 167(L)*185(W)*89(D) mm | ||||
Weight | About 900g (Batteries included) | ||||
Working / Storage Temperature and Humidity |
Operation: -10 ° C ~ 50 ° C, Relative Humidity75% or less (excluding steam) | ||||
Storage: -20 ° C ~ 60 ° C, relative humidity 75% or less (excluding steam) | |||||
Accessories | Normal measuring cables (Green / Black / Yellow: 20m, Red: 40m), Easy measuring probes, Auxiliary earth bars (4 pcs), Coiled cable (4 pcs) USB Adapter, USB Cable, CD Software KEW annotation, R6P * 8, Carrying Bag, Shoulder Strap |