Kyoritsu Kew 6016, 10 Functional Test Device

Earth Resistance test (3 pole test and socket test), the possibility of performing Phase-Ground and Phase-Neutral tests in the socket

Testing the current drawn by the system by testing PSC (expected short circuit current) from the socket

Continuity

Isolation (1000 V)

Loop

PSC (Short circuit current)

PFC (Possible leakage current)

RCD (Residual current relay) test

Voltage

Frequency

Phase Sequence

Computer Connection with USB

The ability to store 1000 data

Technical Properties
Open Circuit Voltage (DC) Short Circuit Current Stage Accuracy
5V ± 20% Greater than 200mA 20/200/2000Ω Automatic Step 0~0.19Ω: ±0.1Ω 0.2~2000Ω: ±(2%rdg+8dgt)
2Ω Buzzer : Alert with Buzzer below 2 Ω when resistance is measured.
Technical Document
Insulation Resistance (High speed measurement)

Open Circuit Voltage (DC)

Current Value Stage Accuracy
250 V+25% -0% 1mA or bigger @ 250kΩ 20/200MΩ Automatic Step 0~19.9MΩ: ±(2%rdg+6dgt) 20~200MΩ:±(5%rdg+6dgt)
500V+25% -0% 1000 V+20% -0% 1mA or large @ 500kΩ 1mA or large @ 1MΩ 20/200/2000MΩ Automatic Step 0~199.9MΩ: ±(2%rdg+6dgt) 200~2000MΩ: ±(5%rdg+6dgt)
Loop Impedance
Function Voltage Rating Nominal Test Current External Loop at 0Ω: Magnitude / Time (at 230V) Stage Accuracy
L-PE 100~260V50/60Hz 20Ω: 6A/20ms 200Ω: 2A/20ms 2000Ω: 15mA/500ms 20/200/2000Ω Automatic Step

230V + 10% -15%: ± (3% rdg + 4dgt) without voltages: ± (3rdg + 8dgt)

L-PE (ATT) 100~260V 50/60Hz L-N: 6A/60msN-PE: 10mA/approximatelly 5s 20/200/2000Ω Automatic Step L-N < 20Ω 230V + 10% -15%: ± (3% rdg + 6dgt) excluding voltages: ± (3rdg + 8dgt)
L-N / L-L 100~500V 50/60HzL-N:100~300V
L-L:300~500V
20Ω:6A/20ms 20Ω 230V + 10% -15%: ± (3% rdg + 4dgt) without voltages: ± (3rdg + 8dgt)
PSC (L-N/L-L) / PFC (L-PE)
Function Voltage Rating Nominal Test current 0Ω External External Loop: Magnitude / Time (at 230V) Step Accuracy
PSC
PFC
PFC (ATT)
100~500V50/60Hz
100~260V50/60Hz
100~260V50/60Hz
6A / 20ms6A / 20ms2A / 20ms15mA / 500msL-N: 6A / 60msN-PE: 10mA / about 5s 2000A/20kA Automatic Step PSC / PFC accuracy is obtained from the measured Loop Impedance specification and the measured voltage specification.
RCD
Function Current Value Step Accuracy
Current Throw

Discard Time

AC Type A Type
X1/2 10/30/100/300/500/1000mA 2000ms -8%~-2% -10%~0% ±(1rdg+3dgt)
X1 10/30/100/300/500/1000mA G:550ms / S:1000ms +2%~+8% 0%~+10% ±(1rdg+3dgt)
X5 10/30/100mA 410ms +2%~+8% 0%~+10% ±(1rdg+3dgt)
Auto Ramp 10/30/100/300/500mA 20%~110% (per10%) G:300ms/S: 500msX10times ±4% ± 10% ±(1rdg+3dgt)
Automatic Test The measurement accuracy depends on each function.
In Measuring Order: X1 / 2 (0 °) → X1 / 2 (180 °) → X1 (0 °) → X1 (180 °) → X5 (0 °) → X5 (180 °)
Measurements with x5 are not performed for RCDs with a nominal current of 100mA or more.
Uc 10/30/100/300/500/1000mA 0.0~100.0V +5%~+15%rdg±8dgt
Voltage Value :230V+10%-15% 50/60Hz
Voltages
Function Voltage Value Measuring Range Accuracy
Voltages 25~500V 25~500V ±(2%rdg+4dgt)
frequence 45~65Hz 45.0~65.0Hz ±(0.5%rdg+2dgt)
Earthing
Measuring Range Accuracy
3 wire earth resistance test 20/200/2000Ω 20Ω: ±(3%rdg+0.1Ω)
100Ω>Auxiliary Earth resistance Automatic step 200/2000Ω: ±(3%rdg+3dgt)
Voltage Value 50~500V, 50/60Hz
Sing Right Phase: "1-2-3" sign, Reverse Phase: "3-2-1" sign
Standarts IEC61010-1: 2001, CAT III.300V Pollution Degree 2, IEC61557 1,2,3,4,5,6,7,: 2007, -10: 2001
IEC61010-031: 2002
Power Source LR6x8
Dimensions 136(L)*235(W)*114(D) mm
Weight 1350g About
Accesories

Extended Test Probe, Distribution Board test probe fuse, Ground Test Probes (5m, 10m, 20m) and auxiliary ground rods, Test Probe Carrying bag, Carrying Case, User Manual, Batteries, USB Adapter with computer software “KEW Report”